¢º
|
3500R/3500L/3600R/3600L/3620R/3620L
: Solid State Electronic Actuators |
Each product of this
series drives and controls a control valve, with a motor driven
by a
full-electronic controller upon receipt of a signal (4 to
20 m ADC) from the controller.
A product of 3500 series, which is of high-end type, executes
critical control by means of
a brushless DC servo, a product of 3600 series or 3620 series
providing superior cost
performance executes control by an AC reversible motor. Furthermore,
a product of 3620
series, which is of motor built-in type, provides excellent
heat radiation effect. In addition,
explosion-proofing approved models are also replete. See
here for models and details of
specification.
- See here
for Table of torque and thrust force.
- See here
for Explosion-proof approved models and specification.
3500R Rotary stem motion type/3500L Linear
stem motion type
Principal uses |
Control
|
Power |
Drive motor |
Brushless DC motor
|
Power supply |
Single phase 100V AC 50/60Hz
|
Power supply
Optional |
Single phase 110/200/220V AC 50/60Hz
|
Motor rating |
Continuous
|
Control mechanism |
Input signal |
4 to 20mA DC
|
Input signal
Optional |
1 to 5V DC/4 to 12mA DC/12
to 20mA DC
|
Opening signal transmission
Optional |
4 to 20mA DC with zero and
span adjustment
|
Resolution |
0.3% (3/1000)
|
Resolution Optional |
0.1% (1/1000)
|
Zero adjust range |
+/-12.5%
|
Span adjust range |
5 to 100%
|
Operation |
Either forward operation or reverse
operation can be selected
|
Ancillary mechanism |
Manual operation mechanism |
Dismountable handle type
|
Sequence output signal |
Output shaft clockwise turned position
(3500R)
Output shaft lowered position (3500L)
|
Sequence output signal
Optional |
Output shaft counterclockwise turned
position (3500R)
Output shaft elevated position (3500L)
|
Overload protection |
With built-in overload protector
|
Space heater
Optional |
* Please contact us for details,
as this matter depends on the power supply voltage.
|
Conditions for installation |
Ambient temperature |
-10 to 50°
|
Ambient temperature
With space heater |
-20 to 40°
|
Mounting position |
Should not be mounted in an inverted
position from the maintenance face.
|
Body portion |
External sheath type |
Protection class IP55 or equivalent
|
Wiring port |
G1/2 (2 places)
|
Wiring port Optional |
Various adaptors can be mounted
|
Installation seat |
Conforms to ISO
|
3600R Rotary stem motion type/3600L Linear stem motion type
Principal uses |
Control
|
Power |
Drive motor |
AC reversible motor
|
Power supply |
Siingle phase 100V AC 50/60Hz
|
Power supply
Optional |
Single phase 110/200/220V AC 50/60Hz
|
Motor rating |
30 minutes
|
Control mechanism |
Input signal |
4 to 20mA DC or 1 to 5V DC
|
Opening signal transmission |
4 to 20mA DC
|
Resolution |
0.8 to 1.0% (1/125 to 1/100)
|
Resolution Optional |
0.4% (1/250)
|
Zero adjust range |
+/-25%
|
Span adjust range |
20 to 100%
|
Operation |
Either forward operation or reverse
operation can be selected
|
Ancillary mechanism |
Control position detection
Optional |
Auxiliary limit switch (voltfree),
maximum points of detection 2 places (3600R)
|
Manual operation mechanism |
Dismountable handle type
|
Overload protection |
With built-in thermal protector
|
Overload protection
Optional |
Overload unit,
Torque switch on closed side (CW direction only, 3600R)
|
Space heater
Optional |
*Please contact us for details, as
this matter depends on the power supply voltage.
|
Conditions for installation |
Ambient temperature |
-10 to 50°
|
Ambient temperature
With space heater |
-20 to 40°
|
Mounting position |
Should not be mounted in an inverted
position from the maintenance face.
|
Body portion |
External sheath type |
Protection class IP55 or equivalent
|
Wiring port |
G3/4 (3600R) G1/2 (3600L)
2 places
|
Wiring port Optional |
Various adaptors can be mounted,
Terminal box (3600L)
|
Installation seat |
Conforms to ISO
|
3620R Rotary stem motion type/3620L Linear stem motion type
Principal uses |
Control
|
Power |
Drive motor |
AC reversible motor
|
Power supply |
Single phase AC100/110V 50/60Hz (+/-5%)
|
Power supply
Optional |
Single phase AC200/220V 50/60Hz (+/-5%)
|
Motor rating |
30 minutes
|
Control mechanism |
Input signal |
4 to 20mA DC or 1 to
5V DC
|
Opening signal transmission |
4 to 20mA DC
|
Resolution |
0.5 to 1.0% (1/200 to 1/100)
|
Resolution
Optional |
0.3% (1/300)
|
Zero adjust range |
+/-25%
|
Span adjust range |
20 to 100%
|
Operation |
Either forward operation or reverse
operation can be selected
|
Save function |
ON/OFF selection by select switch
|
Ancillary mechanism |
Control position detection
Optional |
Auxiliary limit switch (voltfree),
maximum points of detection 2 places
|
Manual operation mechanism |
With handle insertion hole
|
Overload protection |
With built-in thermal protector,
Torque switch (3620R is an option)
|
Space heater
Optional |
* Please contact us for details,
as this matter depends on the power supply voltage.
|
Conditions for installation |
Ambient temperature |
-10 to 50°
|
Ambient temperature
With space heater |
-20 to 40°
|
Mounting position |
Should not be mounted in an inverted
position from the maintenance face.
|
Body portion |
External sheath type |
Protection class IP55 or equivalent
|
Wiring port |
G1/2 (2 places)
|
Wiring port Optional |
Various adaptors can be mounted,
Terminal box
|
Installation seat |
Conforms to ISO
|
|